37
Troubleshooting
Troubleshooting AQUATOP LOGON WP
Malfunction
Cause
Remedy, Action
228: Flow controller water source A W-W heat pump
No flow
A1 Checker whether corresponding sliders are
opened
A2 Check function flow switch (while keeping
groundwater pump running, check switching
point of flow switch by slowly closing/opening
slider)
A3 Check function of groundwater pump
229: Pressure monitor
GHS/geothermal probe/tube
collector system
A B-W heat pump
Brine pressure too low
The module switches the respective unit to
the safety state when a malfunction or error
occurs.
A1 Check brine pressure with manometer
A2 Check function of brine pressure monitor
A3 Recharge brine
A4 Check expansion vessel when recharging brine
(if pressure increases quickly when recharging
brine, expansion vessel malfunction)
A5 If occurring several times, check brine circuit for
leaks
230: Thermo relays
230: Thermo relays brine pump Brine pump / groundwater pump
A Pump failure
A1 Pump blocked
A2 Motor protection was triggered
A3 Defective pump
The module switches the respective unit to the
safety state when a malfunction or error occurs.
A1 Eliminate pump block, determine cause of
block
A2 Check why motor protection was triggered
A21 Check power consumption of pump (ampere)
A22 Check trigger value of motor protection
A23 Check motor protection for defects
A3 Replace pump if defective
Electric company block active External block by utility or electric company No malfunction, HP continues to run once block
period is over.