31
Initial Startup
Parameterization
Configuration 5951 I
Operating action contact H1
-
Normally closed contact (NCC), normally
open contact (NOC
NOC
5952 I
Min. flow setpoint H1
°C 8 120 40
5954 I
Heat demand 10V H1
°C 5 130 60
6007 F
Operating action input
E14, E16
-
NCC NOC NCC
6020 I
Function expansion module 1
-
No function, heating circuit, cooling circuit 1 Heating circuit
6110 F
Time constant, building
h 0 50 10
6120 F
System frost protection
-
OFF ON ON
6200 I
Save sensor
-
No Yes No
6201 F
Delete sensor
-
No Yes No
6204 F
Save parameter
-
No Yes No
6205 F
Reset parameter
-
No Yes No
6212 I
Control number generator 1
- 0 199999 0
6213 I
Control number generator 2
- 0 199999 0
6215 I
Control number storage
- 0 9 19999 0
6217 I
Control number heating
circuits
- 0 199999 2
Failure 6710 I
Reset alarm relays
-
No Yes No
6711 I
Reset heat pump
-
No Yes No
6740 F
Flow temperature 1 alarm
min - - - / 10 240 - - -
6741 F
Flow temperature 2 alarm
min - - - / 10 240 - - -
6800
-
6819
F
Time stamp and error
code, error history 1-18
0 255 Only displays:
Date, time, error code,
error type
Maintenance
Service
7070 I
HP time interval Months
- - - / 1 240 - - -
7071 I
HP time since maintenance Months
0 240 0
7072 I
Max starts compr1 / op hours
- - - - / 0.1 12 - - -
7073 I
Act starts compr1 / op hours
- 0 12 0
7074 I
Max starts compr2 / op hours
- - - - / 0.1 12 - - -
7075 I
Act starts compr2 / op hours
- 0 12 0
7076 I
Spread condens max/week
- - - - / 1 250 - - -
7077 I
Act spread condens max/week
- 0 250 0
7078 I
Spread condens min/week
- - - - / 1 250 - - -
7079 I
Act spread condens min/week
- 0 250 0
7080 I
Spread evap max/week
- - - - / 1 250 - - -
7081 I
Act spread evap max/week
- 0 250 0
7082 I
Spread evap min/week
- - - - / 1 250 - - -
7083 I
Act spread evap min/week
- 0 250 0
7090 I
PWH storage time interval Months
- - - / 1 240 - - -
7091 I
PWH storage since mainte-
nance
Months
0 240 0
7092 I
PWH charge temp HP min
°C 8 80 40
7093 I
Act. PWH charge temp. HP
°C 8 80 -
7141 E
Emergency operation
-
OFF ON OFF
7142 F
Emergency operation function
type
-
Manual Automatic Manual
7150 I
Exterior temp. simulation
°C - - - / -50 50 - - -
7181 I
Customer service phone
Digits 0 16
Control line
Control level
Function
Unit
Min
Max
Factory
settings
Kommentare zu diesen Handbüchern