29
Initial Startup
Parameterization
Cooling
circuit 1
901 E
Operating mode
-
OFF
902 E
Comfort setpoint
°C
Value from control
line 710
907 E
Release
- 24h/day, timer program heating circuit,
timer program 3/HCP,
timer program 4/PWH
24h/day
908 I
Flow setpoint at ExT 25°C
°C 8 35 20
909 I
Flow setpoint at ExT 35 °C
°C 8 35 16
912 E
Cooling limit at ExT
°C 8 35 24
923 I
Min. flow setpoint at ExT 25°C
°C 8 35 18
924 I
Min. flow setpoint at ExT 35°C
°C 8 35 18
945 I
Mixing valve in heating mode
-
Opened Closed Opened
Heating
circuit 2
1010 . . . 1156 (same as heating circuit 1)
Heating
circuit P
1300 E Operating mode heating circuit P - Protective mode, automatic, reduced, comfort Automatic
1310 . . . 1456 (same as heating circuit 1)
Potable water 1610 E
Potable water temperature,
rated setpoint
°C
Value from control
line 1612
TempBwMax 55
1612 E
Reduced setpoint
°C 8
Value from control
line 1610
40
1620 I
Potable water release
-
24h/day, timer program, heating circuit, timer program 4
Timer program 4
1630 I
Load priority
-
Absolute, sliding, none, MC sliding, PC absolute
Absolute
1640 F
Legionella function
-
OFF, periodic, fixed day of week
OFF
Heat pumps
2800 I
Frost protection condens. pump
-
OFF ON ON
2802 I
Flow time condens. pump
s 0 240 10
2803 I
Overrun time condens. pump
s 0 240 10
2815 I
Source temp. min. water
HP (B92)
°C - - - / -20 30 3
2816 I
Source temp. min. brine
HP (B91)
°C - - - / -30 50 -5
2817 I
Switching diff. source protect.
°C 1 10 3
2818 I
Increase source protection temp.
°C 0 10 2
2819 I
Flow time, source
s 0 240 40
2820 I
Overrun time, source
s 0 240 10
2840 I
Switching diff. return temp.
°C 1 20 4
2842 I
Compressor run time, min.
min 0 120 10
2843 I
Compressor standstill time, min.
min 0 120 20
2844 F
Switch off temp. max.
°C 8 100 57
2860 F
Block level 2 at PWH
-
OFF ON OFF
2861 F
Release level 2 below ExT
°C -30 30 -5
2886 F
Compensation heat deficit
-
OFF ON ON
2951 I
Source temp. defrost release
°C 5 20 12
2958 I
No. of defrost cycles, max.
- 0 10 4
2962 I
Duration defrost block
min 0 100 15
2963 I
Time until forces defrost
min 60 600 150
2964 I
Defrost duration, max.
min 1 42 15
2965 I
Evaporator drip time
min 0 10 0
3000 I
Switch off temp. max. cooling
°C 20
60 35
Control line
Control level
Function
Unit
Min
Max
Factory
settings
F = Function E = End User I = Initial Startup